Model Insignia 750 Insignia 1K Insignia 1.5K Insignia 2K
Capacity 750 VA / 480 W 1000 VA / 700 W 1500 VA / 1050 W 2000 VA / 1400W
INPUT
Voltage 110/120 VAC
Voltage Range 81-145 VAC
Frequency Range 60/50 Hz (auto sensing)
OUTPUT
AC Voltage Regulation (Batt. Mode) ±10%
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ± 1 Hz
Waveform (Batt. Mode) Pure Sinewave
Transfer Time Typical 2-6 ms, 10ms max.
BATTERY
Battery Type & Number 12 V / 9 Ah x 1 12 V / 7Ah x 2 12 V / 9 Ah x 2 12 V / 10 Ah x 2
Typical Recharge Time 6 hours recover to 90% capacity
PROTECTION
Full Protection Overload, discharge, and overcharge protection
INDICATORS
LCD Display AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery
ALARM
Battery Mode Sounding every 10 seconds
Low Battery Sounding every second
Overload Sounding every 0.5 second
Battery Replacement Alarm Sounding every 2 seconds
Fault Continuously sounding
PHYSICAL
Dimension, D x W x H (mm) 350 x 146 x 160 397 x 146 x 205
Net Weight (kgs) 6.8 9.0 12.2 13.7
ENVIRONMENT
Humidity 0-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 45dB Less than 55dB
MANAGEMENT
USB & RS-232 Port Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
* Product specifications are subject to change without further notice